INPUT | |
Sensor Type | pt100 100 Ohm @ 0ºC 2 or 3 wire |
Sensor Range | (-200 to 850)ºC (18 to 390) Ohm |
Sensor Connection | Screw Terminal |
Minimum Span (See note 1) | 25ºC |
Linearisation | BS EN 60751 (IEC 751) Standard / JISC 1604 |
Accuracy (See note 2) | ±0.1ºC ±0.05% of Reading |
Thermo Drift | 0.0025% /ºC |
Excitation Current | <200μA |
Lead resisitance effect | 20Ω per leg |
Maximum Lead Resistance | 0.002ºC/Ω |
Note 1 | Any span may be selected, full accuracy is only guaranteed for spans greater than the minimum recommended Span. |
Note 2 | Basic measurement accuracy includes the effects of calibration linearisation and repeatability. |
OUTPUT | |
Type | Two wire (4 to 20 mA) Sink |
Limits | Low 3.8mA; High 21.5mA |
Accuracy | ±0.1ºC ±0.05% of Reading |
Loop effects | ±0.2μA / V measured @ 50Hz 1 V (peak to peak) |
Thermal Drift | ±1μA/ºC Typical; ±1.5μA Max. |
MAx Load | [(Vsupply-10)/20]KΩ |